In the modern in power system, electric power equipment numerous, and various components operation complex, it is easy to appear all sorts of forms of electrical fault, so the relay protection measures must be taken to make the system more stable operation. This paper is to 110 KV power grid to relay protection research and design. This paper according to the characteristics of the power grid the generator, transformer parameters and the setting calculation, through the calculation results confirmed the CT/PT models. Meanwhile, in the paper, the possible all forms of short-circuit current for a detailed calculation. According to this short circuit current parameters, the design adopted phase spacing protection and zero sequence current protection two kind of relay protection measure.But because of the relay protection device may be because of its own defects misoperation, so in this design has also used the automatic reclosing technology, through the automatic reclosing device can reduce this error action as much as possible, so that the whole power system can be more stable operation.希望里边的句子能对你有帮助,可以自己修改下,我也是找人帮你翻译的,望采纳!。
2.220KV电网的继电保护 毕业设计
试读结束,如需阅读或下载,请点击购买>
原发布者:路人
第1章电气主接线电气主接线是变电所电气设计的重要部分,也是构成电力系统的重要环节。电气主接线对电力系统整体及变电所本身运行的可靠性、灵活性和经济性密切相关,并且对电气设备选择、配电装置布置、继电保护和控制方式的拟定有较大影响。变电站主接线根据变电站在电力系统中的地位、负荷性质、出线回路数等条件和具体情况确定。通常变电站主接线的高压侧,应尽可能采用短路器数目教少的接线,以节省投资,变电站低压侧应采用单母分段接线,以便于扩建。对本变电所进行分析,结合对电气主接线的可靠性、灵活性及经济性等基本要求,综合考虑。在满足技术、经济政策的前提下,力争使其技术先进,供电可靠,经济合理的主接线方案。此主接线还应具有足够的灵活性,能适应各种运行方式的变化,且在检修、事故等特殊状态下操作方便、调度灵活、检修安全、扩建发展方便。变电站主接线见图图1-1变电站主接线图第2章电气设备简介2.1主变压器主变压器参数如表:表2-1主变压器参数2.2高压断路器高压断路器选择如下表:表2-2高压断路器选择2.3互感器的选择1、电流互感器主要参数的选择:互感器是电力系统中测量仪表、继电保护等一次设备获取电气一次回路信息的传感器。互感器将高电压、大电流按比例变成低电压(100、100/
3.相间距离保护原理
距离保护是反应故障点至保护安装地点之间的距离(或阻抗)。并根据距离的远近而确定动作时间的一种保护装置。该装置的主要元件为距离(阻抗)继电器,它可根据其端子上所加的电压和电流测知保护安装处至短路点间的阻抗值,此阻抗称为继电器的测量阻抗。当短路点距保护安装处近时,其测量阻抗小,动作时间短;当短路点距保护安装处远时,其测量阻抗增大,动作时间增长,这样就保证了保护有选择性地切除故障线路。
用电压与电流的比值(即阻抗)构成的继电保护,又称阻抗保护,阻抗元件的阻抗值是接入该元件的电压与电流的比值:U/I=Z,也就是短路点至保护安装处的阻抗值。因线路的阻抗值与距离成正比,所以叫距离保护或阻抗保护。距离保护分为接地距离保护和相间距离保护等。
距离保护分的动作行为反映保护安装处到短路点距离的远近。与电流保护和电压保护相比,距离保护的性能受系统运行方式的影响较小。
当短路点距保护安装处近时,其量测阻抗小,动作时间短;当短路点距保护安装处远时,其量测阻抗大,动作时间就增长,这样保证了保护有选择性地切除故障线路。距离保护的动作时间 (t)与保护安装处至短路点距离(l)的关系t=f(l),称为距离保护的时限特性。为了满足继电保护速动性、选择性和灵敏性的要求,目前广泛采用具有三段动作范围的时限特性。三段分别称为距离保护的Ⅰ、Ⅱ、Ⅲ段,它们分别与电流速断、限时电流速断及过电流保护相对应。
距离保护的第Ⅰ段是瞬时动作的,它的保护范围为本线路全长的80~85%;第Ⅱ段与限时电流速断相似,它的保护范围应不超出下一条线路距离第Ⅰ段的保护范围,并带有高出一个△t的时限以保证动作的选择性;第Ⅲ段与过电流保护相似,其起动阻抗按躲开正常运行时的负荷参量来选择,动作时限比保护范围内其他各保护的最大动作时限高出一个△t。
4.求电气专业英语论文一篇
1 距离保护(ZM1-5)1.1 情况 概述距离保护装置是在输电网和变电网中应用得最广泛的一种保护装置。
在配电网中它也变得越来越重要。主要原因如下:*它在线路两端之间的通信通道中的独立性,是因为它是利用本地有效电流和电压信息动作的。
*距离保护在电力网中形成了一个相互关联的有选择性的保护系统(非单元式的保护系统)。这意味着它也可以作为网络中其他主要元件的远后备保护。
现代线路保护的基本要求,比如快速性,灵敏性和选择性,以及在可靠性和安全性方面的严格要求,变得越来越严格。另外,现代距离保护在网络中必须能够与阻抗继电器配合动作,这是一种由不同技术设计而成的继电器(静态或者是机电式继电器)。
较早的阻抗继电器在多数情况下只用于电力线路的相间和三相故障的保护,一些其他保护用于接地故障中。由于这些原因现代距离保护的灵活性非常重要,当它用于一个复杂的网络结构时尤其合适。
比如并列运行的多回线路和辐射网。距离保护的有选择性动作不是依靠线路两端间的通信设备。
距离保护能在远方末端电流互感器处检测到故障。这个功能使它成为那些不能检测到超过反方向末端电流互感器范围以外故障的线路差动保护的一个理想补偿。
距离保护范围在线路REX 5XX的保护、控制和终端监测方面的距离保护装置由3到5个独立的距离保护范围组成,每一个包括了3个接地故障的测量元件和3个相间故障的测量元件。对于各种不同电压等级在不同的电网中,不同的终端要适合不同的要求。
由于这个原因,距离保护装置的一些特征参数各终端之间是不同的(要了解详细内容,请查阅线路保护终端的分类细节)。距离保护区域5不同于其他段在于它动作的快速性。
它比其他距离保护段启动快,而且在不同的系统暂态过程中,由于这个原因误动的可能性就更高了,因此它只适用于以下情况:允许更高越限或者作为具有超过100ms延时的延时距离保护段。线路差动保护的补充在一些线路差动保护终端设备中(如REL 561)距离保护装置能够成为一个有选择性的保护。
同时它是超出反方向末端电流互感器以外故障时的主保护,这个功能由带延时段实现(如II段),它覆盖了所有相邻母线,因此形成了母线的主保护或后备保护。所以超越段应处于持续动作状态。
保护范围为部分线路的保护段(如I段)可以作为线路差动保护的后备。只要差动保护动作这个功能就不需要了。
为了减小I段误动的风险,可以在差动保护拒动时将其投入,差动保护失灵的最大原因就是通信系统故障。由于这个原因用于距离保护的通信方案应该使用另一个通信途径而舍弃用于线路差动保护的那一个方案。
简单参数的整定每一距离保护段基本上包含了作为相对地、相间测量的完全独立的整定参数。这是复杂网络结构中和那些被要求使新配置的距离保护装置适应目前其他类型继电器的网络的一个优势情况。
一套简明的可选择参数适用于反映各种类型故障的相同最大保护范围是一个标准惯例的场合。参看整定参数和整定操作说明表格。
基本特性作为合成到线路REX 5XX保护终端的距离保护装置是一个全方案的距离保护。这意味着在不同范围内对于各种类型故障它都有单独的测量元件。
根据终端类型,它至少由5个独立的阻抗测量范围(详情参看通信规则详文)组成,每一个都是四边形特性,示例插图如图38。RL和XL代表线路电阻和电抗,RF代表保护范围的电阻最大值。
A1.2 Line impedanceAbout this chapterThis chapter describes the line impedance functions in the terminal.1 Distance protection (ZM1-5)1.1 ApplicationGeneralThe distance protection function is the most widely spread protection function in transmission and subtransmission networks. It is also becoming increasingly important indistribution networks. The main reasons for this are:• Its independence on communication links between the line ends, because for its operation,it uses information about the locally available currents and voltages.• The distance protection forms a relatively selective protection system (non-unit protectionsystem) in the power network. This means that it can also operate as a remoteback-up protection for other primary elements in the network.The basic requirements for modern line protection, such as speed, sensitivity and selectivity, with their strict requirements for dependability and security (availability), aregetting more stringent. In addition, modern distance protections must be able to operate in networks with existing distance relays, which are mostly designed in a different technology (static or even electromechanical relays).Older distance relays protect in many cases power lines only at phase-to-phase and three-phase faults. Some other protection is used for phase-to-earth faults.The flexibility of modern distance protection is for this reason very important. This especially applies when it is used in a complex network configuration, for example, on parallel operating multicircuit lines and on 。
5.线路保护的原理中的距离保护
一般的线路是均匀的。那么2113,线路的等效阻抗的大小,就与线路的长度有关。假设线路单位长度的阻抗是z。那么等效阻抗Z=zL。L是线路的长度。
理解以上概念,就不难理解距离保护:
一般线路发生接地5261故障。假设过度电阻为0。那么,我们通过测量电压U和电流I,就可以求出4102线路的主抗,Z=U/I=zL
这样就可以求出故障距离L。通过判定L是否在保1653护范围内,回就可以实现保护。
实际应用中,我们保护范围X是已知的。那么,就会有个最大阻抗Zmax=zX。其保护原理就是:
Z=U/I<Zmax故障点在保护范围内,动作答。
Z=U/I>Zmax故障点在保护范围外,不动作。(为了理解简单,没有考虑可靠性系数问题)参考资料:张保会《电力系统继电保护》
6.最新毕业论文:关于220KV电网继电保护本科毕业论文
去百度文库,查看完整内容> 内容来自用户:教育幼儿教师 本文研究的是关于220KV电网继电保护。
通过本次设计掌握和巩固电力系统继电保护的相关专业理论知识,熟悉电力系统继电保护的设计步骤和设计技能,根据技术规范,选择和论证继电保护的配置选型的正确性并培养自己在实践工程中的应用能力、创新能力和独立工作能力。本次设计是根据湖南生物机电事业技术学院毕业要求而进行的毕业设计。
此次设计的主要内容是220KV电网继电保护的配置和整定,设计内容包括:第一章概论;第二章计算系统中各元件的主要参数;第三章输电线路上TA、TV变比的选择及中性点接地的选择;第四章电力网短路电流的计算;第五章自动重合闸的选择。由于各种继电保护适应电力系统运行变化的能力都是有限的,因而,对于继电保护整定方案的配合不同会有不同的保护效果,如何确定一个最佳的整定方案,将是从事继电保护工作的工程技术人员的研究课题。
总之,继电保护既有自身的整定技巧问题,又有继电保护配置与选型的问题,还有电力系统的结构和运行问题。尤其,对于本文中220KV高压线路分相电流差动保护投运前的现场试验,一直是困扰技术人员的一个问题,由于线路两端距离的限制,现场试验不能像试验室那样方便。
另外,光纤保护在长距离和超高压输电线路上的应用还有一定的局限性,在施工和管理应用上仍存在不足,但是从长远看,随着光纤网络的逐步完善、施工工艺和保护产品技术的((1)双绕组变压器电抗有名值:各绕组的电抗标幺值=Z③3保护的运行方式是以通过保护装置的。
7.继电保护试验的距离保护
用于距离保护定值校验,定性分析保护距离保护各段动作的灵敏性和可靠性。
界面左上边是参数设置,左下边是测试过程中电压电流输出显示,而右上边是测试记录显示,下边依次是接点状态模拟显示及注释。 是自动测试方式,根据测试项目和故障类型的选择,分割成若干个子试验项目,以校验距离保护各个定值。
线路联接将被测保护装置的线圈绕组联接到本装置相应的电流及电压输出端。将被测保护装置的动作接点动作触点联接到本装置的接点输入。
A.相间页1.I段阻抗Z1:设置相间距离I段的阻抗定值:幅值、角度。2.R1 + j X1:设置相间距离I段的阻抗定值:电阻、电抗 。
3.II段阻抗Z2:设置相间距离II段的阻抗定值:幅值、角度。4.R2 + j X2:设置相间距离II段的阻抗定值:电阻、电抗。
5.III段阻抗Z3:设置相间距离III段的阻抗定值:幅值、角度。6.R3 + j X3:设置相间距离III段的阻抗定值:电阻、电抗。
7.IV段阻抗Z4:设置相间距离IV段的阻抗定值:幅值、角度。8.R4 + j X4:设置相间距离IV段的阻抗定值:电阻、电抗。
B.接地页1.接地阻抗Z1:设置接地距离I段的阻抗定值:幅值、角度。2.R1 + j X1:设置接地距离I段的阻抗定值:电阻、电抗 。
3.接地阻抗Z2:设置接地距离II段的阻抗定值:幅值、角度。4.R2 + j X2:设置接地距离II段的阻抗定值:电阻、电抗。
5.接地阻抗Z3:设置接地距离III段的阻抗定值:幅值、角度。6.R3 + j X3:设置接地距离III段的阻抗定值:电阻、电抗。
7.接地阻抗Z4:设置接地距离IV段的阻抗定值:幅值、角度。8.R4 + j X4:设置接地距离IV段的阻抗定值:电阻、电抗。
C.故障页1.A相接地故障:打√者表示选中测试,同时可设置该类故障的故障方向2.B相接地故障:打√者表示选中测试,同时可设置该类故障的故障方向3.C相接地故障:打√者表示选中测试,同时可设置该类故障的故障方向4.AB相间故障:打√者表示选中测试,同时可设置该类故障的故障方向5.BC相间故障:打√者表示选中测试,同时可设置该类故障的故障方向6. CA相间故障:打√者表示选中测试,同时可设置该类故障的故障方向7.三相短路故障:打√者表示选中测试,同时可设置该类故障的故障方向D.项目页1.I段阻抗Z1:设置并选择I段阻抗的4个测试项目。2.II段阻抗Z2:设置并选择II段阻抗的4个测试项目。
3.III段阻抗Z3:设置并选择III段阻抗的4个测试项目。4.IV段阻抗Z4:设置并选择IV段阻抗的4个测试项目。
E.参数页1.Ⅰ段故障电流:设置试验时I段的故障电流。2.Ⅱ段故障电流:设置试验时Ⅱ段的故障电流。
3.Ⅲ段故障电流:设置试验时Ⅲ段的故障电流。4.Ⅳ段故障电流:设置试验时Ⅳ段的故障电流。
5.故障前电流:设置故障前时间内输出的电流,一般为0。6.故障前电压:设置故障前时间内输出的电压。
7.短路合闸角:设置故障发生时刻电压的角度。8.Ux设置:同上F.其他页1.故障启动方式:选择每次子试验的触发方式,提供2个选项:自启动:本次子试验结束后,程序自动进入下一个子试验项目;按键启动:本次子试验结束后,程序自动提醒,等待用户按键,控制是否进入下一个子试验项目。
2.故障前时间:设置每次故障前等待时间,期间输出零状态,范围:0-60秒。3.故障限时:设置每次故障的时间,范围:0-60秒。
4.零序补偿Kr:5.零序补偿Kx:同上,具体关系如下:R0=R1(3Kr+1)X0=X1(3Kx+1)6.跳闸延时:设置模拟断路器的跳闸动作时间,测试仪根据开入量的连接,一旦接受到保护的跳闸信号,经过跳闸延时后,方进入跳闸后的电压电流状态。如果测试仪开入量直接连接断路器的跳位接点,则跳闸延时可取为0。